Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/15/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEMS 1, 2, 5, AND 8 FROM 6/11 INSPECTION HAVE NOT BEEN CORRECTED, NEXT FAILURE WILL INCUR RE-INSPECTION FEE |
| 06/11/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEUTRAL WIRES NOT PERMITTED TO BE PAIRED UNDER SINGLE LUG SCREW 2) CONDENSOR DISCONNECTS NOT PERMITTED TO BE BEHIND UNITS (30" WORK SPACE MINIMUM) 3) INSTALL FIXTURE AT BACK PATIO DOOR 4) INSTALL POST TENSION TAG AT WATER INLET 5) OCCUPANCY SEPERATION DOOR MUST SELF CLOSE AND LATCH 6) UNFINISHED WIRING IN GARAGE 7) 2ND FLOOR T-STAT NOT INSTALLED 8) PROVIDE LADDER FOR ATTIC ACCESS 9) INSTALL SMOKE ALARM AT TOP OF STAIRS |