Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/01/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1) FIX LEAK TO PEX LINE AT KITCHEN 2) INSTALL WASHERS AT WEDGE ANCHORS AT KITCHEN SHEAR TRANSFER 3) DRAFT STOP FURN DOWN 4) SECURE LOOSE ANCHOR BOLTS |
| 04/26/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1) REMOVE SCREEN FROM DRYER VENT T TOP 2) PROVIDE WATER TEST 50 PSI MIN 3) DRAFT STOP KITCHEN 4) REMOVE STAPLES BEHIND REFRIGERENT LINE 5) SUPPORT 90 DEGREE AT VTR 6) NO TEST ON GAS LINE |