Permit: T01CM00696

Parcel: 134220560


Addresses:

6720 E KORALEE ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/28/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
03/26/2001 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/1. USE LONG S WEEP 90 DEGREES WHEN GOING VERTICAL TO HORIZ. 2. CAP OFF VENTS SAN "T"S LAYING FLAT VENT TRAP ARM TO MAIN VENT. 3. DBL. LAV. REQUIRES A 2" LINE. 4. CHECK UPSTREAM MAN HOLE OR C/OUT IN ALLEY F.F. NEEDS TOO BE 1'0" ABOVE OR A BACK WATER VALVE IS REQUIRED. 5. SET BACKS BOTH SIDES PLAN CALLS FOR 7'6" HAVE PLAN CHANGED TO WHAT YOU HAVE. 6. USE SAN T'S IN VERTICAL.