Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. USE LONG S WEEP 90 DEGREES WHEN GOING VERTICAL TO HORIZ. 2. CAP OFF VENTS SAN "T"S LAYING FLAT VENT TRAP ARM TO MAIN VENT. 3. DBL. LAV. REQUIRES A 2" LINE. 4. CHECK UPSTREAM MAN HOLE OR C/OUT IN ALLEY F.F. NEEDS TOO BE 1'0" ABOVE OR A BACK WATER VALVE IS REQUIRED. 5. SET BACKS BOTH SIDES PLAN CALLS FOR 7'6" HAVE PLAN CHANGED TO WHAT YOU HAVE. 6. USE SAN T'S IN VERTICAL. |