Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/25/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NEED 30" WIDE X 36" DEEP CLEARANCE AT SUB-PANEL 2) MISSING FIRE BLOCK AT DROPS 3) NEED TO HAVE C/P ON PLOT PLAN 4) REMOVE PAPER FROM INSULATION 5) REVISE PLAN TO SHOW ALL ELECTRICAL (LIGHTS AND RECEPS) |