Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/10/2001 |
FRAMING |
|
Denied |
DRYER VENT CANNOT HAVE MESH COVERED T CAP, NO PRESSURE TEST ON GAS, FURNACE DUCT RESTRICTED BED ROOM 2 SUPPORT THROUGHOUT, HEADERS MUST BEAR ON TRIMMERS, HTT22 HOLD DOWN NUTS LOOSE, NO COT APP TRUSS DRAWINGS, MECHANICAL DUCT DEFUSER LOCATION AND SIZES NOT PER PLAN |
| 04/05/2001 |
FRAMING |
|
Denied |