Permit: T01CM00681

Parcel: 137338610


Addresses:

1959 W BOTHELL WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM00681

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2001 FRAMING Approved IVRS - Inspection 0000*
04/17/2001 FRAMING Denied IVRS - Inspection 0999*/1) PROTECT ELEC ROMEX CABLE THRU OUT PROVIDE BOXES FOR ALL LIGHT FIXTURES 2) VENT TO ROOF NOT CONNECTED OR SUPPORTED 2ND POSTINELY SUPPORT ALL DRAIN LINES NO P TAPE 3) SECURE CLOSET FLANGE AT 2ND FLOOR 4) VACUMN LINES NOT SECURE AS PER MANF SPEC'S AND NOT PROTECTED THRU OUT 5) AC LINES OUT OF WALL FLUE PIPES IN DIRECT CONTACT WITH COMB MAT 6) EXTEND PLATFORM RE-INSP FEE REQ'D FOR MECH INSPECTION 7) PROVIDE EXHAUST OUTLET FOR VACUMN TO OUTSIDE
04/13/2001 FRAMING Denied IVRS - Inspection 0999*/1) SECURE WATER LINES TO CENTER OF STUD OR PROTECT 2) FAA DBL TOP PLATES AT OVER BORES 3) POST TO BEAM CONNECTIONS 4) PROTECT ELEC WITHIN 1 1/4 FROM STUD 5) SUPPORT 90 DEGREE WITH AN APPROVED METHOD 6) REFRIGERENT LINES OUTSIDE OF WALL 7) DRYER VENT NOT COMPLETE 8) FLOOR SHEATHIN NOT SECURED ROOF NOT DRIED IN FROM COMBUSTIBLE MATERIAL PROVIDE CLEARANCE 9) FLUE PIPES FOR FURNACE