Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/11/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. ISOLATE BOXES AT GARAGE TO HOUSE. 2. PROVIDE BOTES FOR ALL LIGHT FIXTURE SEE NEC. 370-27 OR IRC E 3805.6. 3. SEAL RACE WAY SEC. NEC. 300-7 OR IRCE 3703.6. 4. SECURE ROMEX CABLE BEHIND PANEL WITHIN 8 INCHES OF BOX ISOLATE SECURE. 5. PLUMBING NOT COMPLETE ROOF NOT DRIED IN COMB. MATERIAL |