Permit: T01CM00667

Parcel: 12003065A


Addresses:

4050 S KOSTKA AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/14/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/09/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. PROVIDE GROUNDS TO ALL SNAP SWITCHES AND METALLIC BOXES. 2. PROVIDE BOND WIRE TO GAS LINE. 3. PROVIDE TWO 8' GROUND RODS FOR ELEC. PANEL 6' APART. 4. PROTECT ELEC. THRU OUT.