Permit: T01CM00662

Parcel: 115072340


Addresses:

268 W ADAMS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM00662

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FINAL SUBJECT TO OTHER INSPECTIONS.
02/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*RECEIVED LETTER REGARDING INSPECTION ON 11-26-01 1.) PLEASE FILL ALL UNUSED OPENING IN PANEL "K" 2.) WIRE BOXES NEED TO BE GROUNDED USE HOLE PROVIDED FOR GROUNDING 3.) LOOSE SEALTITE FITTING ON THE ROOF. 4.) PLEASE LABEL A/C DISCONNECTS. 6.) A/C FUSES ARE NOT INSTALLED AT THIS TIME 7.) CONDUIT TO A/C UNIT CAN NOT BE SUPPORTED TO ACCESS PANELS ON UNIT. 8.) MAINTENCE RECEPTACLE ON ROOF TO BE WORKING AND GFI. PROTECTED.