Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00662
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK FINAL SUBJECT TO OTHER INSPECTIONS. | |
02/27/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*RECEIVED LETTER REGARDING INSPECTION ON 11-26-01 1.) PLEASE FILL ALL UNUSED OPENING IN PANEL "K" 2.) WIRE BOXES NEED TO BE GROUNDED USE HOLE PROVIDED FOR GROUNDING 3.) LOOSE SEALTITE FITTING ON THE ROOF. 4.) PLEASE LABEL A/C DISCONNECTS. 6.) A/C FUSES ARE NOT INSTALLED AT THIS TIME 7.) CONDUIT TO A/C UNIT CAN NOT BE SUPPORTED TO ACCESS PANELS ON UNIT. 8.) MAINTENCE RECEPTACLE ON ROOF TO BE WORKING AND GFI. PROTECTED. |