Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK FINAL SUBJECT TO OTHER INSPECTIONS. |
| 02/27/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*RECEIVED LETTER REGARDING INSPECTION ON 11-26-01 1.) PLEASE FILL ALL UNUSED OPENING IN PANEL "K" 2.) WIRE BOXES NEED TO BE GROUNDED USE HOLE PROVIDED FOR GROUNDING 3.) LOOSE SEALTITE FITTING ON THE ROOF. 4.) PLEASE LABEL A/C DISCONNECTS. 6.) A/C FUSES ARE NOT INSTALLED AT THIS TIME 7.) CONDUIT TO A/C UNIT CAN NOT BE SUPPORTED TO ACCESS PANELS ON UNIT. 8.) MAINTENCE RECEPTACLE ON ROOF TO BE WORKING AND GFI. PROTECTED. |