Permit: T01CM00662

Parcel: 115072340


Addresses:

268 W ADAMS ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00662

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/15/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) SUPPORT WIRES ARE NEEDED FOR RECESSED CANS, EXIT LIGHTS 410-16. 2.) 2 X 4 FIXTURES ARE TO BE ATTACHED TO THE GRID 410-16 CITY AMEND 4.) ELECTRIC IS TO BE SUPPORTED INDEPENDENTLY OF THE CIELING WIRES 300-11. 5.)PLEASE SUPPORT CONDUIT AS PER CODE ALSO YOU CAN NOT SUPPORT WITH THHN AS A STRAP. 6.) MISSING JUNCTION BOX COVERS.