Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/15/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) SUPPORT WIRES ARE NEEDED FOR RECESSED CANS, EXIT LIGHTS 410-16. 2.) 2 X 4 FIXTURES ARE TO BE ATTACHED TO THE GRID 410-16 CITY AMEND 4.) ELECTRIC IS TO BE SUPPORTED INDEPENDENTLY OF THE CIELING WIRES 300-11. 5.)PLEASE SUPPORT CONDUIT AS PER CODE ALSO YOU CAN NOT SUPPORT WITH THHN AS A STRAP. 6.) MISSING JUNCTION BOX COVERS. |