Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00662
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
02/15/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) SUPPORT WIRES ARE NEEDED FOR RECESSED CANS, EXIT LIGHTS 410-16. 2.) 2 X 4 FIXTURES ARE TO BE ATTACHED TO THE GRID 410-16 CITY AMEND 4.) ELECTRIC IS TO BE SUPPORTED INDEPENDENTLY OF THE CIELING WIRES 300-11. 5.)PLEASE SUPPORT CONDUIT AS PER CODE ALSO YOU CAN NOT SUPPORT WITH THHN AS A STRAP. 6.) MISSING JUNCTION BOX COVERS. |