Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM00648
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
05/07/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1) CONDENSATE DRAIN NOT TO CODE ON SANYO UNIT SEE 94 UMC CODE MODIFICATIONS 310.4 NOTE 2 2) STRAP ALL FLEX DUCT EVERY 4' WITH MIN. 1 1/2" WIDE STRAPS | |
05/04/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1) NEED TO SEE CONDENSATE DRAIN FOR SANYO AIR HANDLER. 2) MARK DATA PLATES ON A/C UNITS WITH PROPER HEAT KIT AND FUSE UNITS ACCORDINGLY | |
04/26/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* OK FOR TEMP C OF O |