Inspection History: ELECTRIC - TEMPORARY POLE
Permit Number - T01CM00648
Inspection Description - ELECTRIC - TEMPORARY POLE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2001 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection 0000*OK TO CLEAR TEMP POWER SP # 101, CHECK SPACE # ON METER, SHOULD BE # 101 PER PERMIT. CHECK CLEARANCE FROMWALL FOR TRANSFORMER (SEE FRONT COVER LABEL) SHOULD BE SPACED 6" FROM WALL. INSTALL DEAD FRONTS ON PANEL BOARDS PRIOR TO ENERGIZING FOR SAFETY. | |
04/12/2001 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection 0245* 1) INSTALL BOND BUSHINGS OR BOND LOCKNUTS IN TRANSFORMER. 250-30,94 2) BOND JUMPERS FOR BOND BUSHINGS AT SERVICE AND PANELS UNDERSIZED, SHOULD BE SIZED PER EQUIPMENT GROUNDS. 3) INSTALL GFCI RECEPTICLES FOR CONSTRUCTION POWER. 4) INSTALL REJECTION CLIPS AT SERVICE DISCONNECT 5) ISOLATED GROUND NOT INSTALLED PER PLAN |