Permit: T01CM00648

Parcel: 127090080

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY POLE

Permit Number - T01CM00648

Inspection Description - ELECTRIC - TEMPORARY POLE

Inspection Status - Approved

Date Description Inspector Results Comments
04/13/2001 ELECTRIC - TEMPORARY POLE Approved IVRS - Inspection 0000*OK TO CLEAR TEMP POWER SP # 101, CHECK SPACE # ON METER, SHOULD BE # 101 PER PERMIT. CHECK CLEARANCE FROMWALL FOR TRANSFORMER (SEE FRONT COVER LABEL) SHOULD BE SPACED 6" FROM WALL. INSTALL DEAD FRONTS ON PANEL BOARDS PRIOR TO ENERGIZING FOR SAFETY.
04/12/2001 ELECTRIC - TEMPORARY POLE Denied IVRS - Inspection 0245* 1) INSTALL BOND BUSHINGS OR BOND LOCKNUTS IN TRANSFORMER. 250-30,94
2) BOND JUMPERS FOR BOND BUSHINGS AT SERVICE AND PANELS UNDERSIZED, SHOULD BE SIZED PER EQUIPMENT GROUNDS. 3) INSTALL GFCI RECEPTICLES FOR CONSTRUCTION POWER.
4) INSTALL REJECTION CLIPS AT SERVICE DISCONNECT 5) ISOLATED GROUND NOT INSTALLED PER PLAN