Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00635
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK SERVICE WALL & SOFFIT. | |
| 06/11/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0935*1)STRAP NM CABLE WITHIN 12" OF BOX OF FITTING.2)LOOSE CABLE CONNECTORS.3)SMOKE DETECTOR TO BE NO LESS THAN 3' FROM RETURN. | |
| 06/04/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 2ND FLOOR. | |
| 06/01/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)LOOSE CONNECTOR AT PANEL ANDF SUPPORT CABLES.2)NEED TO REMOVE SHEET ROCK ON DEMISING WALL FOR INSPECTION. 3)SUPPORT DATA/TVAS PER CODE.4)SHEATHING TO BE AT LEAST 1/4" INTO BOXES. |
|
| 05/17/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL,OK 1ST FLOOR. | |
| 05/15/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* |