Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 06/04/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/01/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1)STAPLE NM CABLE AS PER CODE WITHIN 12" OF BOX/CAN.2)SHEATHING TO BE AT LEAST 1/4" INTO BOXES.3)LOOSE CONNECTS AT PANEL AND SUPPORT CABLES.4)NEED TO REMOVE SHEET ROCK ON DEMISING WALL FOR INSPECTION. |
| 05/27/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/17/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL,OK 1ST FLOOR. |
| 05/15/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/08/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1) INSTALL FLEX FOR WATER HEATERS AT ROUGH ELECTRIC 2) PLEASE INSTALL GROUND TAILS AT ROUGH ELECTRIC 3) NEED STRAIN RELIEF CONNECTORS NOT SNAP BUSHINGS 370-17(B) 4) BACK TO BACK PENETRATIONS ON FIRE WALL SUBJECT TO BLDG INSPECTOR DETERMINATIONS 5) NEED STRAIN RELIEF CONNECTORS AT PANEL 373-5(C) 6) SECURE NM CABLES AS PER CODE 7) HOOD NOT TO BE ON KITCHEN APPLIANCE CIRCUIT 210-23(A) |