Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00634
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/04/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/01/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)STAPLE NM CABLE AS PER CODE WITHIN 12" OF BOX/CAN.2)SHEATHING TO BE AT LEAST 1/4" INTO BOXES.3)LOOSE CONNECTS AT PANEL AND SUPPORT CABLES.4)NEED TO REMOVE SHEET ROCK ON DEMISING WALL FOR INSPECTION. | |
| 05/27/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 05/17/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL,OK 1ST FLOOR. | |
| 05/15/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 05/08/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) INSTALL FLEX FOR WATER HEATERS AT ROUGH ELECTRIC 2) PLEASE INSTALL GROUND TAILS AT ROUGH ELECTRIC 3) NEED STRAIN RELIEF CONNECTORS NOT SNAP BUSHINGS 370-17(B) 4) BACK TO BACK PENETRATIONS ON FIRE WALL SUBJECT TO BLDG INSPECTOR DETERMINATIONS 5) NEED STRAIN RELIEF CONNECTORS AT PANEL 373-5(C) 6) SECURE NM CABLES AS PER CODE 7) HOOD NOT TO BE ON KITCHEN APPLIANCE CIRCUIT 210-23(A) |