Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2001 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*CHECK FOR SMOKE DETECTORS NEAR SUPPLIES. |
| 05/15/2001 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* 1) DRYER VENTS PIPE INSULATED WITH KRIMPED END REVERSED, AT 90 DEGREE BEND AT WALL. KRIMPED END AT FIRST RISER IS GOING TO COLLECT LINT. THIS IS INCORRECT, NEEDS TO BE REVERSED 2) REF. LINE BUNDLES DO NOT ALLOW COPPER TO TOUCH STEEL STRAPS |