Permit: T01CM00628

Parcel: 14026002F


Addresses:

2200 E DREXEL RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T01CM00628

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/01/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) PLEASE TIGHTEN OR REPLACE UNISTRUT CLAMPS ABOVE WASHER BOX 2.) ALL CORRECTIONS MADE OK WATER TEST OK 3.) OK TO COVER.
07/31/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) MISSION BAND ON SHOWER DRAIN OK TESTED OK 2.) CLEAN-OUT EXTENSION SHALL BE MADE WITH WYE BRANCH. FITTING. 3.) NO CHANGE IN HANGERS, AND SUPPORTS.
07/25/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) A NO HUB BAND IS NOT AN APPROVED CONNECTOR FOR ABSXN/H (FLOOR DRAIN, ROOF DRAIN) 2.) ROOF DRAINS ARE BACK PITCHED.
07/23/2001 PLUMBING - ROUGH, SOIL Denied 1.) HORIZONTAL VENTING BELOW THE FLOOD RIM OF THE FIXTURE IS LIMITED TO WHERE STRUCTURAL CONDITIONS PROHIBIT ANYOTHER INSTALLATION. THE SHOWER DRAIN IS WITHIN THE TRAP ARM DISTANCE ALLOWED, AND SHOULD BE INSTALLED PER PLAN. IF NOT, SHOW ME WHY IT CANNOT BE INSTALLED CONVENTIONALLY. 2.) BACK PITCH ON 2" ABS TO AUTOMATIC WASHER. 3.)NO HUB BAND NOT APPROVED FOR TRANSITION FROM N/H TO ABS. 4.) 3" ROOF DRAIN AND 3" OVERFLOW DRAIN CANNOT BE COMBINED. PLEASE INSTALL PER PLAN. 5.) DON'T FORGET DWV PIPING TO BE TESTED TO TEN FEET.