Permit: T01CM00625

Parcel: 12709012C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00625

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
03/09/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935* 1) DID NOT USE INDEPENDANT SUPPORT. CANNOT DOUBLE UP SUPPORT SIZEMICS TO CEILING GRID SUPPORTS. READ WRITE UP 3-5-01 2) THERE ARE STILL UN SUPPORTED MC. 3) A REFEE IS ASSESED. PAY REFEE PRIOR TO NEXT INSP.
03/08/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1) CONTRACTOR HAS NOT COMPLIED WITH LAST INSP. WRITE UP. 2) SUPPORT MC, CONDUIT, AND BOXES PER NEC. 3) DO NOT SUPPORT MC AND 1/2" FLEX TO OTHER CONDUITS FOR SUPPORT. MUST HAVE SUPPORT FROM BLDG STRUCTURE. 4) A RE INSP. FEE WILL BE CHARGED IF NOT IN COMPLIANCE BY NEXT INSP.
03/05/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1) MC CABEL AND CONDUIT MUST BE SUPPORTED PER CODE (NEC) EMT-348-13
MC-334-10 2) SIZEMIC WIRES USED TO SUPPORT CONDUIT, BOXES , ETC. MUST BE INDEPENDANT OF CEILING GRID WIRES AND MUST ALSO LOOP THRU GRID 3) EM. BATTERY PACKS NOT INSTALLED PER PLAN, EXIT LIGHTS? 4) CALL FOR REINSP. WHEN DONE DO NOT COVER CEILING