Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/08/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*EAST UNIT: 1) HI VOLTAGE FUSED DISCONNECT LOCATED UNDER A/C PHGE. RELOCATE SWITCH TO ACCESSABLE LOCATION BRACE AS NECESSARY. EAST AND CENTER UNITS: 2) TERMINATE CONDENSATE DRAIN INTO RAIN GUTTER. NOTES: PAINT ALL PVC CONDENSATE PIPING A) COLD WATER DRAINING ON HOT ROOF SURFACE DESTROYS ROOF. B) UNPROTECTED PVC PIPING (PLASTIC UNPAINTED) BREAKS WITH SUN UVA AND UVB RAYS. WATER RUNS ON ROOF |
|
| 03/07/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000$ ROOF TOP UNITS. WILL RETURN 3-8-01 OCCUPANT AGREES TO ROOF TOP INSP AFTER RAIN. |