Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM00609

Parcel: 11446015A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM00609

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/05/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1) 4 SQUARE BOX J BOX NORTH EAST OF PLATFORM IS OVER FILLED, SEE TABLE 370-16 NEC 2) J BOXES NORTH EAST OVER FILLED 3) MC CABLE STILL NOT STRAPPED UNDER PLATFORM.(PREVIOUS WRITE UP 3-2-01) 4) TEMINATE MC CABLE PROPERLY INTO BOXES
03/02/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* SUPPORT MC CABLE WITH IN 12" EACH BOX AND EVERY 6' IN NEW WALLS AND UNDER NEW PLATFORM 334-10 NEC