Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00609
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/05/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1) 4 SQUARE BOX J BOX NORTH EAST OF PLATFORM IS OVER FILLED, SEE TABLE 370-16 NEC 2) J BOXES NORTH EAST OVER FILLED 3) MC CABLE STILL NOT STRAPPED UNDER PLATFORM.(PREVIOUS WRITE UP 3-2-01) 4) TEMINATE MC CABLE PROPERLY INTO BOXES | |
03/02/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* SUPPORT MC CABLE WITH IN 12" EACH BOX AND EVERY 6' IN NEW WALLS AND UNDER NEW PLATFORM 334-10 NEC |