Permit: T01CM00599

Parcel: 125010710


Addresses:

2640 E 9TH ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
05/11/2001 ROOF NAILING Approved IVRS - Inspection 0000*
05/01/2001 ROOF NAILING Denied IVRS - Inspection 0999*/1) OSB ROOF SHEATHING MUST BE NAILED AT 6" OC AT ALL SUPPORTED ENDS AND EDGES 2) OSB ROOF SHEATHING MUST SPAN 2 BAYS 3 JOISTS 3) SUPPORTING 2 X 4 STRINGERS BEARING ON STEEL MEMBERS MUST HAVE ALL SPLICES BEAR ON SUPPORTING MEMBERS 4) OSB SHEATHING MUST BE INSTALLED PER PENDICTULAR TO SUPPORTING JOIST NOT PARALLEL 5) YOU MUST PROVIDE A SPECIAL INSP REPORT FOR ALL STEEL WELDING