Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00598
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 05/22/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) GAS LINE MUST BE ELECTRICALLY BONDED 2) FURNACE/WATER HEATER VENT NOT IN 3) PROVIDE 100 SQ" HIGH AND LOW COMBUSTION AIR 4) FURNACE PLATFORM NOT IN 5) PORCH BEAM REQUIRES POST UNDER EAST END 6) FIRE WALL IN GARAGE REQUIRES STUDS AT 16" ON CENTER AND NAIL BLOCKS FOR TOP EDGE 7) FIRE BLOCK DROP CEILING IN GARAGE 8) DRYER VENT UNDERSIZE 9) PROVIDE NAIL PROTECTION FOR ALL PLUMBING WITHIN 1 1/4" OF STUD SURFACE 10) PROVIDE CLOSET WRAP FOR ALL ABS PLUMBING THAT WILL BE IN CONTACT WITH CONCRETE 11) DUCT RESTRICTED AT KITCHEN DEFUSER AND AT ENTRY 12) ANCHOR BOLTS LOOSE THROUGHOUT 13) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS 14) WATER CLOSET FLOOR FLANGES MUST BE INSTALLED 15) DUCTS RESTRICTED THROUGHOUT. MUST HAVE MINIMUM RADIUS OF ONE DUCT DIAMETER. DUCT NOT COMPLETE 16) REVISE PLAN FOR ADDED 220VAC CIRCUIT IN GUEST QUARTERS 17) COULD NOT LOCATE MECHANICAL PLAN 18) BEDROOM WINDOW SILL HEIGHT CANNOT EXCEED 44" |