Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T01CM00598
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2001 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection 0000* | |
| 09/07/2001 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection 0999*/ 1) REINFORCING STEEL CANNOT BE IN CONTACT WITH SOIL. ISOLATE ALL HORIZONTAL STEEL FROM REBAR STAKES IN SOIL 2) UFER GROUND CLAMPS LOOSE ON REBAR 3) 3 INCHES CLEARANCE REQUIRED BETWEEN REBAR AND SOIL-MANY AREAS IN CONTACT 4) PLAN CALLS FOR HPA HD22 HOLDOWNS HSA3522 INSTALLED. PROVIDE PROOF OF EQUALITY | |
| 08/08/2001 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection 0000*/ 1) NORTH AND WEST WALL OK, AREA MARKED ON PLAN PAGE 2 |