Permit: T01CM00590

Parcel: 141085320

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/19/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*O.K. FOR C OF O
07/18/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) CHECK DISCONNECTS FOR PROPER FUSING 2.) REPLACE RUBATEX ON 3/4" REFER LIVE 3.) VENT ON DRAIN TRAPS MUST BE DOWNSTREAM OF TRAPS. 4.) ISOLATE COPPER FROM STEEL. 5.) HP-5 NOT FUSED PROPERLY 6.) ANCHOR REFER LINES TO REDWOOD CORRECT & RECALL FOR FINAL.
07/17/2001 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/13/2001 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*NOT READY CALL FOR FINAL WHEN ALL A/C EQUIPMENT IS COMPLETED.
06/29/2001 MECHANICAL - FINAL Denied