Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/07/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
OFFICES & MAIN W/HOUSE LITING. |
| 07/18/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NEED PANEL SCHEDULE FIRE PUMP NOT DONE. |
| 07/17/2001 |
ELECTRIC - FINAL |
|
Denied |
THE DISCONNECTS SERVING AIR HANDLING EQUIPMENT ARE REQUIRED TO BE IDENTIFIED MARKED WITH THE PANEL # LETTER AND CIRCUITS FEEDING THE SWITCH. THE # OR UNIT NAME SERVED BY THE SWITCH IS NOT A CODE REQUIREMENT. SEE ART. 110-22 ART 110-22 AND 110-21 MARKING AND IDENTIFICATIONS OF CIRCUITS THE INDEXES AT EACH PANEL MUST BE MARKED WITH THE AREA THEY SERVE |
| 07/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0255*1.) FIRE SAPPRESSION SYSTEM IS NOT READY. 2.) LABEL ALL DISCONNECTS W/SERVING PANEL AND CIRCUIT #'S 3.) ADD MINI PANEL SCHEDULES TO PANEL DOORS. |
| 06/22/2001 |
ELECTRIC - FINAL |
|
Cancelled |
IVRS - Ri canceled |