Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2001 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 05/08/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0230* THE ELECTRIC SERVICE NEEDS THE FOLLOWING CHANGES/ADDITIONS: 1) THE NEUTRAL MUST BE BONDED TO THE METAL OF THE ENCLOSURES AT THE MAIN SWITCH. THE BOND IN THE METER CAN WILL NOT BE INSPECTABLE ONCE TEP SEALS THE CAN DOOR 2) BOND THE NIPPLE BETWEEN METER CAN AND SWITCH (ON THE METER SIDE ALOS.) BOTH ENDS MUST BE BONDED 3) DRIVE A 2ND GROUND ROD SET 6' AWAY FROM THE 1ST. PERMANENT SERVICES REQUIRE TWO RODS |