Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 03/13/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. NO TRUSS DRAWINGS ON SITE. 2. HOLD DOWN BY ENTRY MISSED STUD. 3. HOLDOWN AT S.E. CORNER MISSED STUD. 4. HOLD DOWN AT S.W. CORNER ONLY HALF NAILED. 5. PORCH LEDGER NOT CLIPPED PER 8/SD2. 6. HOLD DOWN AT REAR CENTER OF HOUSE HALF NAILED. 7. TRUSS EXCESS OF 24" O.C. S.E. HIP. NO ACCESS TO SECOND FLOOR ROOF. YOU MUST PROVIDE LADDER. |