Permit: T01CM00555

Parcel: 13609014B


Addresses:

10355 E 29TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/02/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* IDENTIFY 1) GUTTERWITH SOURCE FEEDER, SWITCH, AND LOCATION 2) ALL PANELS WITH SOURCE AND LOAD INFO.
3) TRANSFORMERS WITH SOURCE AND LOAD
4) MAIN SWITCH AT UTILITY ROOM
BOND: 1) INCOMING CONDUIT AT GUTTER 2) TOP OF EACH NIPPLE AT SERVICE SWITCH IN GUTTER 3) NO DOUBLE LUGGING IN UNIT A & B SWITCH BOXES
SUPPORT: 1) STRAP MISSING ABOVE MAIN SWITCH PANEL NOTE: I'M GOING TO ASK PLAN CHECK IF ANOTHER SWITCH IS NECESSARY AT GUTTER