Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00555
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
03/29/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* IDENTIFY 1) GUTTERWITH SOURCE FEEDER, SWITCH, AND LOCATION 2) ALL PANELS WITH SOURCE AND LOAD INFO. 3) TRANSFORMERS WITH SOURCE AND LOAD 4) MAIN SWITCH AT UTILITY ROOM BOND: 1) INCOMING CONDUIT AT GUTTER 2) TOP OF EACH NIPPLE AT SERVICE SWITCH IN GUTTER 3) NO DOUBLE LUGGING IN UNIT A & B SWITCH BOXES SUPPORT: 1) STRAP MISSING ABOVE MAIN SWITCH PANEL NOTE: I'M GOING TO ASK PLAN CHECK IF ANOTHER SWITCH IS NECESSARY AT GUTTER |