Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/09/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
| 02/06/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) CIRCUIT BREAKER IS TOO LARGE AT 90AMP. 60AMP IS MAX. 2) PAINT EXPOSED PVC WITH LATEX PAINT 3) IF TERMINATING CONDENSATE INTO THE SIDE OF A WASTE VENT, YOU MUST USE AN APPROVED FITTING. CORRECT AND RECALL FOR FINAL |