Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/06/2001 |
FRAMING |
|
Partial Approval |
AC REFRIGERENT LINES OUT OF WALL AT NORTH EAST SIDE 2ND FLOOR SOLE PLATE, ANCHOR PAHGD MISSING FRONT 3 CAR GARAGE AT SWEST CORNER FURNACE FLUE PIPE IN DIRECT CONTACT WITH COMB MATERIAL, DRAFT STOPS IN TWO CHASES UP STAIRS AT SUPPLY AIR THRU ROOF FRAME SEE CONTRACTOR |
| 04/05/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/INSULATION HAS BEEN INSTALLED IN ALL WALLS AND SOME CEILINGS, BEFORE RE-INSPECTION. |
| 04/04/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. FULL BEARING REQ'D AT GARAGE 6X GLU LAM. 2. REMOVE SLACK FROM 6X LAM STRAP. 3. ADD POSTS AT BEAM BY STAIRS BATH ROOM. 4. FIRE BLOCK CHASE BY REAR S.G.D. AND THRU OUT. 5. HIP JACK MISSING HANGER 2ND FLOOR. 6. LEVEL FUR PLATE FORM. 7. NAIL #4 SHEAR PER PLAN. |
| 04/02/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. LEAKING IN ABS AND PEX LINES. 2. ABS BENDS EXCEED 135 DEGREE. 3. FHA STRAPS NOT NAILED AT OVERKNOTCHES. 4. 6/SD2 NOT SHEAR TRANSFERS NOT DONE 5. PLATFORM FOR FURNACES NOT DONE. 6. BACK PATIO LEDGER NOT SECURE FROM PULL AWAY. 7. HOLDOWNS 2 MISSING AT 3 CAR GARAGE TOO MANY ITEMS TO LIST. 8. DRAFTSTOPS POST TO BEAMS NOT COMPLETE. |