Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/27/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1. ANCHOR BOLTS MISSING AT INTERIOR AND EXTR TWO PER PANEL. 2. ELEC. BOX NOT SECURE AT HALL BATH. 3. ISOLATE ROMEX BEHIND PANEL NO BUNDLING. 4. REMOVE SCREEN AT DRYER VENT T TOP 5. PROVIDE ALL DETAIL SHEETS. |
| 03/23/2001 |
FRAMING |
|
Denied |
1. 1 1/2 DRAIN AT HALL BATH EXCEEDS LENGTH REQUIRED PER UPC 42 INCHES TO TRAP. 2. PEX LINE IN DIRECT CONTACT WITH METAL FRAMING STRAP. 3. ANCHOR BOLTS REQUIRED AT SHEAR PANELS. SEE SCHEDULE. 4. SECURE DBL TOP PLATE AT GARAGE OVER LAP PER UBC CHAP. 23. 5. COMPLETE ROOF FLASHING AND CLEARANCE LO COMB. MAT. AT FLUE PIPES. 6. NO WATER TEST. |