Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM00477
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
09/10/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) FIRE TAPE OPENINGS FOR FIRE DAMPERS. INSTALL ANGLE IRON PROPERLY. FIRE DAMPER MISSING ANGLE IN DEXASCAN ROOM. 2.) MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE UNIT ACCORDINGLY 3.) SEAL AROUND ELEC. FLASHINGS. RECALL FOR FINAL INSPECTION. | |
07/30/2001 | MECHANICAL - FINAL | Not ready for Inspection |