Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2001 | PLUMBING - ROUGH, SOIL | Approved | TEST OK ON UNDERGROUND SOIL ONLY. INSTALLED AS PER PLANS OK TO BACKFILL | |
| 04/09/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* PLEASE PROVIDE APPROVED AS BUILD DRAWING BY NEXT INSP. OR INSTALL AS PER APPROVED PLAN | |
| 04/06/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) 4" HORIZONTAL WASTE HAS EXCEEDED 135 DEGREES AT BOTH PLACES. SEE SEC. 707.5 94 UPC 2) RE TEST SYSTEM 3) WILL REQUIRE A REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM BEFORE NEXT INSP. 4) NOTE: I WILL ACCEPT FLAT VENT SYSTEM FOR WATER CLOSET DUE TO STRUCTURE CONDITION |