Permit: T01CM00477

Parcel: 12101103J


Addresses:

6270 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/10/2001 PLUMBING - ROUGH, SOIL Approved TEST OK ON UNDERGROUND SOIL ONLY. INSTALLED AS PER PLANS OK TO BACKFILL
04/09/2001 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000* PLEASE PROVIDE APPROVED AS BUILD DRAWING BY NEXT INSP. OR INSTALL AS PER APPROVED PLAN
04/06/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999* 1) 4" HORIZONTAL WASTE HAS EXCEEDED 135 DEGREES AT BOTH PLACES. SEE SEC. 707.5 94 UPC 2) RE TEST SYSTEM 3) WILL REQUIRE A REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM BEFORE NEXT INSP.
4) NOTE: I WILL ACCEPT FLAT VENT SYSTEM FOR WATER CLOSET DUE TO STRUCTURE CONDITION