Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM00469
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 02/26/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO INSULATE AND DRYWALL 2) DOOR WAY NOT INTO EXISTING BUILD TO PLAN OR REVISE PLAN TO AS BUILT 2) EXHAUST FOR GAS HEATER CANNOT BE WITHIN 4 FEET OF DOOR OR WINDOW 3) TEMP GLASS NOT IN | |
| 02/25/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) WRAP ABS PLUMBING THAT WILL BE IN CONTACT WITH CONCRETE WITH APPROVED CLOSET WRAP 3) NAIL PROTECT ALL PLUMBING THAT IS WITHIN 1 1/4" OF STUD SURFACES 4) GROUND ALL METAL ELECTRIC BOXES 5) GAS HEATER VENT NOT INSTALLED 6) PROVIDE INSTALLATION DATA ON HEATER | |
| 11/23/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) BANG PLATE ALL ELECTRICAL AND PLUMBING WITHIN 1 1/4 FROM EDGE OF STUD | |
| 07/13/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) WATER CLOSET NOT PROPERLY VENTED, VENT MUST BE ABOVE CENTER LINE OF WASTE 2) LAV NOT VENTED-TUB NOT VENTED 3) WATER TEST PLUMBING 4) MAKE UP ELECTRIC GROUNDS AND GROUND METAL BOXES 5) INSTALL SMOKE DETECTOR CIRCUIT 6) BATHROOM REQUIRES 20 AMP CIRCUIT | |
| 06/19/2001 | FRAMING | Denied | IVRS - Inspection 0999* |