Permit: T01CM00469

Parcel: 12215201A

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/18/2002 FRAMING Approved IVRS - Inspection 0000*
02/26/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) OK TO INSULATE AND DRYWALL 2) DOOR WAY NOT INTO EXISTING BUILD TO PLAN OR REVISE PLAN TO AS BUILT 2) EXHAUST FOR GAS HEATER CANNOT BE WITHIN 4 FEET OF DOOR OR WINDOW 3) TEMP GLASS NOT IN
02/25/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) WRAP ABS PLUMBING THAT WILL BE IN CONTACT WITH CONCRETE WITH APPROVED CLOSET WRAP 3) NAIL PROTECT ALL PLUMBING THAT IS WITHIN 1 1/4" OF STUD SURFACES 4) GROUND ALL METAL ELECTRIC BOXES 5) GAS HEATER VENT NOT INSTALLED 6) PROVIDE INSTALLATION DATA ON HEATER
11/23/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) BANG PLATE ALL ELECTRICAL AND PLUMBING WITHIN 1 1/4 FROM EDGE OF STUD
07/13/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) WATER CLOSET NOT PROPERLY VENTED, VENT MUST BE ABOVE CENTER LINE OF WASTE 2) LAV NOT VENTED-TUB NOT VENTED 3) WATER TEST PLUMBING 4) MAKE UP ELECTRIC GROUNDS AND GROUND METAL BOXES 5) INSTALL SMOKE DETECTOR CIRCUIT 6) BATHROOM REQUIRES 20 AMP CIRCUIT
06/19/2001 FRAMING Denied IVRS - Inspection 0999*