Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/26/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TO INSULATE AND DRYWALL 2) DOOR WAY NOT INTO EXISTING BUILD TO PLAN OR REVISE PLAN TO AS BUILT 2) EXHAUST FOR GAS HEATER CANNOT BE WITHIN 4 FEET OF DOOR OR WINDOW 3) TEMP GLASS NOT IN |
| 02/25/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) WRAP ABS PLUMBING THAT WILL BE IN CONTACT WITH CONCRETE WITH APPROVED CLOSET WRAP 3) NAIL PROTECT ALL PLUMBING THAT IS WITHIN 1 1/4" OF STUD SURFACES 4) GROUND ALL METAL ELECTRIC BOXES 5) GAS HEATER VENT NOT INSTALLED 6) PROVIDE INSTALLATION DATA ON HEATER |
| 11/23/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BANG PLATE ALL ELECTRICAL AND PLUMBING WITHIN 1 1/4 FROM EDGE OF STUD |
| 07/13/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WATER CLOSET NOT PROPERLY VENTED, VENT MUST BE ABOVE CENTER LINE OF WASTE 2) LAV NOT VENTED-TUB NOT VENTED 3) WATER TEST PLUMBING 4) MAKE UP ELECTRIC GROUNDS AND GROUND METAL BOXES 5) INSTALL SMOKE DETECTOR CIRCUIT 6) BATHROOM REQUIRES 20 AMP CIRCUIT |
| 06/19/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |