Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM00456
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2003 | PLUMBING - FINAL | Approved | PLBG. FINAL IS OK OK FOR C OF O. |
|
05/13/2003 | PLUMBING - FINAL | Denied | BACKFLOW DEVICE AT ICE MAKER IS 009 REQUIRES DRAIN TESTING, CERIFICATION 2.) NAPKIN DISPENSER ENCROACHES ON 18" AT HC WATER CLOSETS. 3.) ALL SINKS REQUIRE CLEAN OUTS CORRECTED AT RM 140. |
|
05/12/2003 | PLUMBING - FINAL | Partial Approval | OK FOR TEMP C/O | |
05/08/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
04/30/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*CAN NOT BUSH DOWN FLOW CONTROL OUTLET FOR TRIPLE COMPT SINK. 2.) MUST EXPOSE C.O. FOR SINK IN RM #140. 3.) ICE MACHINE REQUIRES A 007 BACKFLOW PREVENTER TESTED & CERTIFIED. 4.) INDIRECT WASTE FOR PREP SINK MUST HAVE 1" AIR GAP. 5.) H.C. LAVATORY HEIGHT MAX 34" A.F.F. 29" BOTTOM A.F.F. 6.) OK FOR TEMP C OF O. |
|
04/22/2003 | PLUMBING - FINAL | Denied | RESOLVE CONFLICT WITH PLAN REGARDING LOCATION OF ROOF DRAINS AND POSSIBLE DELETION OF A DRAIN. | |
04/03/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*HAVE PLUMBER COMPLETE HIS PUNCH LIST BEFORE CALLING IN FINAL INSPECTION. |