Permit: T01CM00456

Parcel: 117084090


Addresses:

1080 S 10TH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM00456

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*CLOSET RINGS HAVE BEEN SET IN EAST RESTROOM.
02/10/2003 PLUMBING - INTERMEDIATE Partial Approval 1.) CLOSET FLANGES, SOUTH SIDE ONLY OK
2.) HAVE PLUMBER CAP OFF ALL OPEN DRAIN LINES IT WILL ELIMINATE THE SMELL AND THE INSANITARY CONDITION.
02/10/2003 PLUMBING - INTERMEDIATE Partial Approval 1.) CLOSET FLANGES, SOUTH SIDE ONLY OK.
2.) HAVE PLUMBER CAP OFF ALL OPEN DRAIN LINES IT WILL ELIMINATE THE SMELL AND THE INSANITARY CONDITION.
02/09/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) #10 APPROVES YARDWATER LOCATION.
2.) 3" PVC YARDWATER FROM METER TO SHUT OFF VALVE IN SERVICE BOX OK OK TO BACKFILL.
3.) INTERMEDIATE NOT READY.
01/17/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) ROOF DRAINS ALONG NORTH WALL OK.
2.) WATER PIPING TO WATER HEATER OK
REFER TO INSTALLATION STD #2 FOR TEMPORARY VALVES.
3.) GAS PRESSURE TEST OK.
4.) RE-ROUGHED CLOSET FLANGES OK
OK TO COVER.
NEED TO SEE CLOSET FLANGES.
12/31/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) N/H THRU ROOF OK
2.) COPPER OK OK TO COVER WALLS
3.) NED TO SEE CLOSET FLANGES
4.) WHERE PLUMBER HAS REROUGHED WATER CLOSETS I WANT TO SEE CONNECTION AND WATER TEST.
12/16/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*N/H DWV THRU ROOF WATER TEST OK
2.) COPPER IN KITCHEN AND HOT ,DOWN CORRIDOR OK PRESSURE TEST OK.
3.) OK TO COVER WALL DONT FORGET GAS PIPING.
12/09/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*GREASE TRAP INSTALL OK OK TO COVER.
12/05/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
A.) GREASE TRAP 1. BLK IRON PIPE NOT PERMITTED BELOW GRADE. (DWV) 2.) WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN LINE. IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE CENTER LINE OF SUCH PIPE, DOWN STREAM OF THE TRAP BEING SERVED.
B.) ROOF DRAINS ON SOUTH, EAST & WEST SIDE OK WATER TEST OK.
11/25/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SOUTH AND WEST BATHROOMS AND SINKS OK N/H DWV THRU ROOF OK NEED TO SEE CLOSET FLANGES OK TO COVER THIS AREA ONLY.