Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM00456
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2002 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
07/10/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) KITCHEN AREA N/H DWV UNDERGROUND OK WATER TEST ONE RISER TO 10 FEET OK 2.) OK TO BACKFILL THIS AREA 3.) CALL FOR PRE - POUR. | |
07/09/2002 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*1.) TEST BALL BLEW OUT NO WATER TEST ON KITCHEN DWV 2.) SOILS WET AT CONNECTIONS BETWEEN DRAIN AND VENT FOR FLOOR DRAIN WITH UG VENT. 3.) DO NOT COVER UNTIL WATER TEST IS APPROVED. | |
07/08/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* | |
06/11/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) N/H UNDERGROUND OK WATER TEST ONE TEN FOOT RISER OK 2.) BLDG DRAIN ATTACHES DIRECTLY TO EXISTING HCS STUB. 3.) CHECK ELEVATION OF MANHOLE COVER VX FFE. AND DELETE BACKWATER VALVE IF NEEDED. PER 710.1 94UPC. 4.) CALL FOR PRE-POUR INSPECTION. |