Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00456
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/25/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* SEE NOTE PAGE FOR NOTES. 1.) LIGHT POLES NOT GROUNDED. 2.) DISCONNECT FOR AIR HANDER BY RECEPTION DESK IN VIOLATION OF WORKING CLEARANCE. SEE ART 110-26. N.E.C. 3.) CONDUITS IN ROOMS ALONG NORTH CORRIDOR ABOVE CEILING STILL NOT SUPPORTED PROPERLY, SEE 348-13 N.E.C. 4.) J-BOXES ON ROOF STILL NOT SUPPORTED, PER WRITE UP NOTE #3 4-22-03. 5.) GATE OPERATORS NOT COMPLETE AT LOADING DOCK. 6.) A RE-INSP. FEE IS ASSESED PER LAST INSP. WRITE UP. PLEASE PAY RE-FEE 201 N. STONE PRIOR TO FUTURE INSP. |
|
04/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) NO COMPLIANCE WITH NOTES #2. 2.) NO PERMANENT PNAEL SCHEDULES. 3.) SUPPORT CONDUITS MCCABLE IN AREAS ABOVE CEILINGS PRIOR TO CALLING IN NEXT INSPECTION. 4.) LIGHT POLE BASES UNDERGROUND CONDUIT IN BACK OF BLD. NEVER INSPECTED. EXPOSE FOR INSP. 5.) A REINSPECTION FEE WILL BE ASSESSED IN NOT IN COMPLIANCE NEXT INSPECTION. 6.) SCREW FIXTURES TO GRID OR CLIPS PER 410 NEC. |
|
04/22/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*CONDUITS IN MULTI PURPOSE ROOM NOT SUPPORTED PER 348-13 NEC. ALSO IN GYM BETWEEN FIXTURES. 2.) UNCOVER CEILINGS IN UNINSPECTION AREAS. 3.) CONDUIT FOR AC-2 ON ROOF NOT SUPPORTED,ALSO J-BOXESFOR EX FANS LOOSE COUPLINGS CONNECTORS. |