Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*/ 1) NEXT INSPECTION IS SHEETROCK |
| 07/10/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE FLUE VENT AT WATER HEATER 2) WILL NEED TO SEE VENT PENETRATION AT ROOF 3) OK-TO INSULATE AND SHEET ROCK EXCEPT AT WATER HEATER |
| 07/08/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE BLOCKING BETWEEN RAFTERS TO PROTECT FROM LATERAL ROTATION AT 3/8 EAVE BOARDS AS PER PLAN 2) PRESSURE TREATED WOOD NOT INSTALLED AS PER PLAN AT TOP PLATE PROVIDE PROTECTION WITH APPROVED SEALER TREATMENT 3) SERVICE ENTRANCE CLEARANCE NOT PROVIDED WILL REQUIRE SERVICE EXTENSION PERMIT, SEE NEC 230-24BX2 |