Permit: T01CM00431

Parcel: 14027050D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM00431

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK TO CLOSE OUT - ELECTRICAL SERVICE AND EQUIP. HAVE BEEN REMOVED
02/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NO ELECTICAL PLANS-SEE NOTES FROM PREVIOUS INSPECTIONS
02/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/03/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*OK TO CLEAR.NOT ENERGIZED NO MAIN TEST OR POWER TEST. DO NOT CONTINUE TO CALL FOR FINAL UNTIL YOU HAVE TESTED YOUR SYSTEM AND CAN PROVIDE THE TEST RESULTS FOR THE MAIN CIRCUIT BREAKERS.
07/27/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*TO RECEIVE POWER 1.) POST A BOND FOR TEMP. POWER & FUEL TESTING. 2.) INSTALL ALL FUSES. MUST BE MANUFACTURER,CLASS, & TYPE SPECIFIED BY ENGINEER. 3.) HAVE SYSTEM ENERGIZED AND HAVE THE MAIN CIRCUIT BREAKERS TESTED. SUBMIT COPY OF TEST RESULTS TO INSPECTOR. 4.) COORDINATE TRANSFORMER INSTALLATION AND CONNECTION W/TEP.