Permit: T01CM00426

Parcel: 103080090

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/21/2001 FRAMING Approved IVRS - Inspection 0000*
06/18/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) PLUMBING NOT COMPLETE 2) NO WATER PRESSURE 3) SECURE PEX THRU OUT 4) FIRE BLOCKS THRU OUT 5) SECURE ROMEX 6) FIRE STOP COLUMNS THRU OUT 7) SECURE GAS LINE 8) GAS NOT COMPLETE AT FIREPLACE 9) STRAP VERSA LAM AT KITCHEN TO KING STUDS AND CLIP KING STUDS 10) 1" CLEARANCE REQUIRED AT FLUE VENT 11) PROVIDE DAMPER AT EXHAUST FANS 11) DRAIN AT TUB 13) SECURE BOTTOM PLATE AT BRG WALL 14) ELECTRICAL AT REAR PORCH 15) PROVIDE ALT HD'S AT REAR REQUIRES DOUBLE STUD 16) ALL AD'S REQUIRE FULL LENGTH DOUBLE STD'S THRU OUT AND NAILED WITH 16 SQUARE NAILS PER PLAN 17) NAIL TJI TO HANGERS AT TRIPLE TJ'S IN LIVING ROOM