Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* OK TO BACKFILL TRENCH | |
| 04/03/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* PAY REFEE | |
| 04/02/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) 3" WASTE LINE FOR GREASE TRAP EXCEEDS 135 DEGREES WILL REQUIRE FLOOR C.O. 2) REVISED DRAWING FOR WASTE AND VENT SYSTEM MUST BE APPROVED BY COT PLAN CHECKER 3) GREASE TRAP NOT INSTALLED AS PER REVISED DRAWING 5) PROVIDE WATER TEST FOR G.T. | |
| 03/22/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* NOT READY | |
| 03/21/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) SITE PLAN DOES NOT SHOW METER AND WATER LINE TO SOUTH OF BLDG. 2) POC OF NEW BLDG DRAIN HAS FERNCOS MUST USE SPECIALTY COUPLING FERNCO COUPLINGS ARE FOR EXTERIOR OF STRUCTURE ONLY. 3) WET VENTS FOR LAVATORYS MUST BE VERTICAL DRAINAGE ONLY SEE SEC 908.1 94 UPC 4) TRAP ARM FOR FLOOR SINK EXCEEDS MAX. DISTANCE SEE TABLE 10-1 94 UPC 5) FLAT VENT FOR GREASE TRAP MUST BE ABOVE 0 LINE OF HORIZONTAL DRAIN. SEE SEC. 905.2 94 UPC 6) WILL REQUIRE REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM FOR GREASE TRAP BEFORE NEXT INSP. 7) 1 FLOOR SINK NEEDS SPECIALITY COUPLING 8) NOTE: CHECK FOR APPROVAL OF GREASE TRAP LOCATION FROM HEALTH DEPT. |
|
| 03/19/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* |