Permit: T01CM00395

Parcel: 114469370

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/01/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/31/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1)BREAKER LOCK-OUTS FOR APPLIANCES NOT PROPER TYPE.2)SO CORD THRU T-BAR CEILING NOT APPROVED WIRING METHOD.MUST BE HARD WIRED WITH CONDUIT AND DISC. SW. AND SUPPORTED.3)DO NOT STACK OR STORE ITEMS IN FRONT OF PANELS,DISC,SWITCHES.
05/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*INSTALL DISCONNECTS OR BREAKER LOCKOUTS ON ALL APPLIANCES, EXCEPT CORD CONNECTED EQUIP.
05/23/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1)COMPLETE WIRING CONNECTIONS TO ALL APPLIANCES WITH DISCONNECTS AND/OR/LAYOUT DEVICES ON CIRCUIT BREAKERS FOR APPLIANCES.2)LABLE DISSCONNECT SWITCHES,PANELS,ETC. AS TO DESIGNATION.3)TO AVOID RE-INSPECTION FEE,DON'T CALL TILL JOB IS READY FOR FINAL.
05/21/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*