Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/31/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1)BREAKER LOCK-OUTS FOR APPLIANCES NOT PROPER TYPE.2)SO CORD THRU T-BAR CEILING NOT APPROVED WIRING METHOD.MUST BE HARD WIRED WITH CONDUIT AND DISC. SW. AND SUPPORTED.3)DO NOT STACK OR STORE ITEMS IN FRONT OF PANELS,DISC,SWITCHES. |
| 05/29/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*INSTALL DISCONNECTS OR BREAKER LOCKOUTS ON ALL APPLIANCES, EXCEPT CORD CONNECTED EQUIP. |
| 05/23/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1)COMPLETE WIRING CONNECTIONS TO ALL APPLIANCES WITH DISCONNECTS AND/OR/LAYOUT DEVICES ON CIRCUIT BREAKERS FOR APPLIANCES.2)LABLE DISSCONNECT SWITCHES,PANELS,ETC. AS TO DESIGNATION.3)TO AVOID RE-INSPECTION FEE,DON'T CALL TILL JOB IS READY FOR FINAL. |
| 05/21/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |