Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/17/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*N.E.C. SECTION 110-22 REQUIRES THAT THE DISCONNECT SWITCHES AND CIRCUIT BREAKERS SERVING TRANSFORMERS, AND EQUIPMENT BE IDENTITFIED WITH THEIR POINT OF ORIGIN. PANEL AND CIRCUIT # MUST BE PLACED ON EACH SWITCH WITH PERMANENT METAL #'S OR TAG. DO NOT USE MAGIC MARKER. |
| 09/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) NEED TO VERIFY NEUTRAL BOND IN X-FORMER. 2.) NEUTRALS AND GROUNDS ARE TIED TO NEUTRAL BARIN PANEL. 3.0 NO COMPLIANCE WITH OTHER ITEMS LAST INSPECTION. 4.) COULD NOT LOCATE PERMIT/PLANS. |
| 06/29/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* |