Permit: T01CM00376

Parcel: 130140230


Addresses:

4220 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM00376

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*N.E.C. SECTION 110-22 REQUIRES THAT THE DISCONNECT SWITCHES AND CIRCUIT BREAKERS SERVING TRANSFORMERS, AND EQUIPMENT BE IDENTITFIED WITH THEIR POINT OF ORIGIN. PANEL AND CIRCUIT # MUST BE PLACED ON EACH SWITCH WITH PERMANENT METAL #'S OR TAG. DO NOT USE MAGIC MARKER.
09/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) NEED TO VERIFY NEUTRAL BOND IN X-FORMER. 2.) NEUTRALS AND GROUNDS ARE TIED TO NEUTRAL BARIN PANEL. 3.0 NO COMPLIANCE WITH OTHER ITEMS LAST INSPECTION. 4.) COULD NOT LOCATE PERMIT/PLANS.
06/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*