Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00375
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
02/27/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1) SIZEMIC WIRES NOT INSTALLED EAST ENTRY FIXTURE. 2) DISCONNECT FOR NEW A.H. UNIT IN VIOLATION OF WORKING SPACE 110-26 NEC 3) DO NOT TILE UNDER A.H. UNIT YET. |