Inspection Status: Partial Approval
Inspection History: BOILER UNFIRED PRESSURE VESSEL
Permit Number - T01CM00360
Inspection Description - BOILER UNFIRED PRESSURE VESSEL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2002 | BOILER UNFIRED PRESSURE VESSEL | Partial Approval | IVRS - Inspection 0000*JOB WILL BE FINALED WHEN STORAGE ARE GROUNDED AS PER ISSUE WITH RON LOHORMAN. | |
01/09/2002 | BOILER UNFIRED PRESSURE VESSEL | Denied | ||
01/03/2002 | BOILER UNFIRED PRESSURE VESSEL | Denied | IVRS - Inspection 0999*MANCHESTER NB 566698 200 PSI SV200PSI YR 2000. NPS BOTTOM #3 NB 5763 5500 PSI SV 5500/5765 2 CENTER. SAME 5766 #1 TOP. NO PLANS ON SITE. 1.) CLAMPS HOLDING HIGH PRESSURE LINE FROM TANKS TO COMPRESSOR ARE TOO TIGHT TO ALLOW FOR EXPANSION. 2.)STORAGE TANK CAN NOT BE REMOVED WITHOUT MORING OTHER EQUIPMENT FOR REPLACEMENT. 3.) CNG NOT GROUNDED. | |
10/24/2001 | BOILER UNFIRED PRESSURE VESSEL | Partial Approval | IVRS - Inspection 0000*PRESSURE OK AT 8000 PSI. 1.) NEED LAFTEY VALVES REPLACED W/LOCKOUTS 2.) NEED A RECOVERY SYSTEM INSTALLED. |