Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00360
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
01/09/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) INSTALL 1/O BOND TO NEUTRAL BUSS IN GUTTER PER PLAN. 2.) INSTALL MAIN BOND JUMPER IN SERVICE DISCONNECT. PER ART 250 N.E.C. | |
01/03/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) COMPLETE SEALING OF SEAL-OFF FITTINGS 2.) NEED TO SEE INSIDE DISPENSER (LOCKED) 3.) RE ATTACH STRAPS FOR GROUND WIRE AT SERVICE 4.) PLANS NOT ON SITE.5.) TRIED TO CALL TWICE # AT MESSAGE, GOT MESSAGE RECORDER. | |
11/21/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
11/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999$PARTIAL OK TO CLEAR TEMP SERV. CNG PLANT 1.) 225A FUSES REQUIRED AT SER.2.) RUN 1/0 CU GROUND TO NEUTRAL AT GUTTER 2. 3.) SEALS TO BE FILLED AT GNG PLANT. ALL OPEN SEALS TO BE FILLED FOR FINAL. SEALS AT C & G PLANT DISPNSER CONTROLL SHACK. 4.) CNG DISPENSER APPROVED BY ENGINEER ON FILE. |