Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) PLBG FINAL IS OK 2.) OK FOR C OF O. |
| 12/12/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) WATER HTR P & T DRAIN HAS TRAP IN LINE. DRAIN MUST HAVE GRAVITY FLOW. 2.) SEE NOTE #5 AS REQUESTED. |
| 12/05/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) H.C. WATER CLOSET HANDLES MUST BE ON OPEN SIDE OF RM (ADA SPECS) 2.) LAVATORY H.C. MUST BE MIN 29" FROM 34" MAX TO TOP OF LAV (ADA SPECS) 3.) WATER HTR REQUIRES A EXPANSION TANK DUE TO CLOSED SYSTEM 4.)P & T DRAIN CAN NOT HAVE FLEX IN LINE AND PROVIDE UNION 5.) MUST CAULK LAVATORY SPLASH BACK. |