Permit: T01CM00355

Parcel: 12615011C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00355

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
03/13/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
03/07/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0250* 1) ADD SUPPORTS TO ALL ELECTRICAL BOXES AND CONDUITS ABOVE CEILING. SOME ARE JUST LYING ON GRID. 2) ADD NAIL PLATES TO / OVER MC CABLE WHERE THE DISTANCE FROM THE SURFACE OF THE STUD TO MC IS LESS THAN 1 1/4". ESPECIALLY IN 2X2 STUD WALLS
FRONT RECEPTION WALL IS OK TO DRYWALL. CORRECT AND RE CALL