Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00355
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
03/13/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
03/07/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0250* 1) ADD SUPPORTS TO ALL ELECTRICAL BOXES AND CONDUITS ABOVE CEILING. SOME ARE JUST LYING ON GRID. 2) ADD NAIL PLATES TO / OVER MC CABLE WHERE THE DISTANCE FROM THE SURFACE OF THE STUD TO MC IS LESS THAN 1 1/4". ESPECIALLY IN 2X2 STUD WALLS FRONT RECEPTION WALL IS OK TO DRYWALL. CORRECT AND RE CALL |