Permit: T01CM00353

Parcel: 133231610


Addresses:

7150 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01CM00353

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*FINAL OK S.T.O.I CORRECTION HAVE BEEN MADE AS PER LAST REQUEST.
07/11/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) SINK REQUIRES TO HAVE A C.O.
05/31/2001 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*1)PLUMBING FINAL FOR PHOTO LAB AREA IS OK.2)FIXTURES FOR AUTOMOTIVE DEPT OK.
05/30/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1)WATER HEATER MUST HAVE EXPANSION TANK DUE TO CLOSED SYSTEM.2)WATER HEATER P AND T DRAIN CAN NOT HAVE FLEX LINE.3)ABS FITTINGS ON WASTE AND VENT SYSTEM MUST BE REMOVED AND REPLACED WITH PVC FITTINGS.THE GREEN TRANSISION GLUE IS APPROVED FOR EXTERIOR OF STRUCTURE ONLY.4)BACK FLOW PREVENTER REQUIRES A DRAIN INDIRECT TO FLOOR DRAIN.5)FLOOR DRAIN REQUIRES A FUNNEL FOR INDIRECT WASTE RECEPTOR FOR P AND T AND BACK FLOW PREVENTER DISCHARGE DRAIN.6)REQUIRE TEST AND CERTIFICATION FOR BACK FLOW DEVICE.7)MUST ANCHOR SINK TO CABINET.8)MUST SECURE 3/4 COPPER WATER LINE IN COLUMN.