Permit: T01CM00341

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/30/2001 FRAMING Approved IVRS - Inspection 0000*
05/22/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) REVISIONS: FOR SHEAR WALLS, WORKING THRU CITY FOR CITY STAMP, SAW ORIGINALS, STAMPED BY ENGINEER OF RECORD 2) CHECK A-3 FOR ATTIC/VENT SIZE AND LOCATION 3) NAIL ALL EXT SHEATHING WALLS S/WEST CORNER, REV CALLS FOR 4"-12" WITH 8DS SEE EQUIVALENTCHART LEFT WITH PERMIT CHECK ALL SHEAR NAILING 4) BLOCK DUCT WORK IN FURNACE, ROOM, MOVE WIRE AWAY FROM FLUE BLOCK OFF RETURN PLENIUM FOR INSULATION 5) TIGHTEN ALL AD NUTS 6) TIE BAY WINDOW WALLS TOGETHER, WITH 2 X AND NAILS 7) DOUBLE STUD UNDER GIRDER 8) NEED TRUSS DRAWINGS ON SITE TO CHECK INTERIOR BEARING PTS 9) KITCHEN WALL MISSING FIRE/BLOCKING 10) MOVER CONDENSATES AWAY FROM CAN LIGHTS EAST CLOSET 11) NO LADDER TO ACCESS MECHANICAL AREAS
05/18/2001 FRAMING Denied